| Product name: | FKN12-12D/630-20 Indoor AC High Voltage Load Switch | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor high-voltage load switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
serial number |
project |
unit |
FKN12-12D/630-20 |
FKN12-12D.R/100-31.5 |
|
one |
rated voltage |
kV |
twelve | |
|
two |
rated frequency |
Hz |
fifty | |
|
three |
rated current |
A |
six hundred and thirty |
one hundred |
|
four |
Lightning impulse withstand voltage |
kV |
Ground and phase to phase 75, isolated and disconnected 85 | |
|
five |
1-minute power frequency withstand voltage |
kV |
To ground and phase 42, isolate and disconnect 48 | |
|
six |
Rated thermal stability current |
kA |
20(4S) | |
|
seven |
Rated dynamic stable current |
kA |
fifty | |
|
eight |
Rated closing current (peak value) |
kA |
fifty |
|
|
nine |
Rated short-circuit breaking current |
kA |
thirty-one point five | |
|
ten |
Rated transfer current |
kA |
one point five | |
|
eleven |
Maximum breaking current (reference value) |
kA |
one point eight | |
|
twelve |
Disconnect the capacity of the no-load transformer |
Kva |
one thousand two hundred and fifty | |
|
thirteen |
Rated cable charging current |
A |
ten | |
|
fourteen |
Rated active load current breaking times |
time |
>100 | |
|
fifteen |
The time when the impactor triggers the load switch to open |
S |
>0.06 | |
|
sixteen |
Grounding switch thermal stability current |
kA |
20(2S) |
20(2S) |
|
seventeen |
Grounding switch thermal stability current (peak) |
kA |
fifty |
fifty |
|
eighteen |
Electric motor operating power supply voltage |
V |
AC220、DC48 | |
|
serial number |
project |
unit |
FKN12-12D/630-20 |
FKN12-12D.R/100-31.5 |
|
one |
Auxiliary contact opening distance |
mm |
>155 | |
|
two |
Synchronization of three-phase opening and closing |
ms |
<3 | |
|
three |
Just divided speed |
m/s |
>2.8 |
two point eight0+0.4 |
|
four |
Just closed speed |
m/s |
>3.8 | |
|
five |
Grounding switch fracture distance |
mm |
145 ± 5 | |
|
six |
main circuit resistance |
μΩ |
<120 |
<300 |
|
seven |
Maximum operating force distance |
N.m |
<160 |
<180 |
|
serial number |
Model number |
Rated current for melting (A) |
Capacity of transformer (kVA) | |
|
UK model |
National standard model | |||
|
one |
SDLAJ-12 |
XPNT□-12 |
sixteen |
100,125,160 |
|
two |
twenty |
two hundred | ||
|
three |
twenty-five |
two hundred and fifty | ||
|
four |
thirty-one point five |
three hundred and fifteen | ||
|
five |
forty |
four hundred | ||
|
six |
SFLAJ-12 |
fifty |
five hundred | |
|
seven |
sixty-three |
630,800 | ||
|
eight |
eighty |
one thousand | ||
|
nine |
SSLAJ-12 |
one hundred |
one thousand two hundred and fifty | |
|
ten |
SKLAJ-12 |
one hundred and twenty-five |
one thousand and six hundred | |
Outline and installation dimension diagram