HomeYour location:HomeHigh voltage electrical appliancesHigh voltage load switchIndoor high-voltage load switch → FZRN23-12D High voltage vacuum load switch
Column tabs 
Product name: FZRN23-12D High voltage vacuum load switch
specification: FZRN23-12D High voltage vacuum load switch
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Indoor high-voltage load switch
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-13916500500

Email 91way@163.com
Wechat 13916500500(Wechat)


FZRN23-12D High voltage vacuum load switchDetailed product description:Column tabs
Overview
FZN23-12 series vacuum load switch and combination device, suitable for three-phase AC 50Hz. 10kV distribution system. It has the advantages of no pollution, no fire and explosion hazards, and can be operated frequently. It can be used as the main component of ring main units, box type substations or other types of switchgear, for the control and protection of power equipment such as transformers, cables, overhead lines, etc. It is widely used in power distribution systems such as factories, residential areas, high-rise buildings, schools, parks, etc.
FZRN23-12D High Voltage Vacuum Load Switch Model Description
Environmental conditions for use
Altitude not exceeding 1000M;
Environmental temperature: maximum+40 ℃; Minimum -15 ℃;
Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%;
Environmental conditions: No corrosive gases, flammable gases, obvious water vapor, and no frequent severe vibrations.

Main electrical and mechanical parameters of vacuum load switch and its combination electrical equipment

Table 1 Technical Parameters of Load Switches

serial number
name
unit
data
load switch
combined electrical apparatus
one
rated voltage
kV
twelve
two
Rated insulation level
Power frequency withstand time, ground/isolation fracture
kV
42/48
Thunder ground impact requires relative pressure to the ground/isolation fracture
kV
75/85
three
rated current
A
630/800 125
four
Rated active load breaking current, rated closed-loop breaking current
A
630/800 125
five
Rated short-time withstand current (2S)
kA
twenty
six
Rated short-circuit closing current, rated peak withstand current
kV
fifty
seven
Rated cable charging breaking current
A
twenty-five
eight
Rated open circuit no-load transformer
kVA
1600 1600
nine
Rated breaking and handover current
A
- 2000
ten
Rated short-circuit breaking current of fuse
kA
- 31.5
eleven
mechanical life
time
5000 5000
twelve
Total breaking time
Ms
not more than 100
thirteen
Overload breaking capability
A
five thousand

Table 2 Technical Parameters of Load Switches

serial number
name
unit
numerical value
remark
one
Interphase center distance
mm
210±3
two
contact gap
mm
10±1
three
Contact itinerary
mm
3±1
four
Three phase closing asynchrony
ms
<2
five
Three phase closing asynchrony
ms
<2
six
Bouncing time of closing contact
ms
<2
seven
Average closing speed
m/s
0.6±0.2
eight
Average opening speed
m/s
1.0±0.2
nine
Accumulated allowable wear thickness of moving contact
mm
three
ten
Open distance between dynamic and static contacts
mm
>160


Installation dimensions of FZRN23-12D high-voltage vacuum load switch
Installation of FZRN23-12D High Voltage Vacuum Load Switch Bottom Plate

FZRN23-12D High Voltage Vacuum Load Switch

FZRN23-12D High voltage vacuum load switch
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference