FZN12-10D/630 Indoor vacuum load switchDetailed product description:Column tabs
FZN12-10D/630-50 indoor AC high voltage load switch (hereinafter referred to as FN12-10D load switch) is a three-phase high voltage switchgear with a rated voltage of 10KV and a rated frequency of 50Hz. It is used for switching load current, closed-loop current, no-load transformer and cable charging current, and short-circuit current. Load switches equipped with grounding switches can withstand short-circuit currents.

FZN12-10 (R) D/100-31.5 AC high voltage load switch fuse combination (referred to as FN12-10 (R) D combination) is an indoor high voltage switchgear that combines FN12-10D load switch with S □ LAJ-12 (XRNT □ -10) high voltage current limiting fuse. It can reliably disconnect any current up to the short-circuit current; The load switch disconnects the working current, the fuse disconnects the short-circuit current, and jointly disconnects any overcurrent between the working current and the full short-circuit current. At the same time, the fuse uses its impactor to open the load switch.

Main technical parameters of FZN12-10D/630 indoor vacuum load switch

serial number

project

unit
numerical value
FN12-10D/630
FN12-10(R)D/630
one
rated voltage
KV
ten
two
rated frequency
Hz
fifty
three
rated current
A
six hundred and thirty
one hundred
four
Lightning impulse withstand voltage
kV
Ground and phase to phase 75, isolation and disconnection 85
five
1-minute power frequency withstand voltage
kV
Ground and phase 42, isolation and disconnection 48
six
Rated thermal stability current
kV
20(4S)
seven
Rated dynamic stable current
kV
fifty
eight
Rated closing current (peak value)
kV
fifty
fifty
nine
Rated short-circuit breaking current (expected value)
kA
thirty-one point five
ten
Maximum I2. t at critical breaking current
A2S
According to the characteristic curve of the fuse
eleven
Minimum breaking current
kA
According to the characteristic curve of the fuse
twelve
Rated transfer current
kA
one point five
thirteen
Maximum breaking current (reference value)
kA
one point eight
fourteen
Disconnect the capacity of the no-load transformer
kVA
one thousand two hundred and fifty
fifteen
Rated cable charging current
A
ten
sixteen
Rated active load current breaking times
time
>100
seventeen
The time for the impactor to trigger the load switch to open the circuit breaker
S
>0.06
eighteen
Grounding switch thermal stability current
kA
20(2s)
20(2s)
nineteen
Grounding switch thermal stability current (peak)
kA
fifty
fifty
twenty
Electric motor operating power supply voltage
V
AC/DC 110, 220


FZN12-10D/630 indoor vacuum load switch appearance and installation dimensions


FZN12-10D/630 Indoor Vacuum Load Switch Outline Dimensional Drawing

FZN12-10D/630 Indoor vacuum load switch
Product Category