| Product name: | NAL-12/12R type load switch | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor high-voltage load switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
Name |
unit |
NAL-12D |
NAL-12DR | |||||
|
one |
rated voltage |
kV |
twelve |
twelve | |||||
|
two |
rated frequency |
Hz |
fifty |
fifty | |||||
|
three |
rated current |
A |
630(1250) |
one hundred | |||||
|
four
|
rated |
1-minute power frequency withstand voltage |
To the ground, alternating with each other |
kV |
forty-two |
forty-two | |||
|
Insulation
level |
isolation gap |
forty-eight |
forty-eight | ||||||
|
Lightning impulse withstand voltage (peak value) |
To the ground, alternating with each other |
seventy-five |
seventy-five | ||||||
|
isolation gap |
eighty-five |
eighty-five | |||||||
|
five |
Rated short-circuit withstand current
(Dynamic Stable Current) |
load switch |
kV
|
fifty |
|||||
|
grounding switch |
sixteen |
||||||||
|
six |
Rated short-circuit duration
(Thermal stability time) |
load switch |
S
|
two |
|||||
|
grounding switch |
two |
||||||||
|
seven |
Rated short-circuit closing current (peak) |
kV |
fifty |
||||||
|
eight |
Active load breaking current |
A |
six hundred and thirty |
||||||
|
Closed loop breaking current |
six hundred and thirty |
||||||||
|
Rated breaking current |
5% active load breaking current |
thirty-one point five |
|||||||
|
Cable charging current |
ten |
||||||||
|
Disconnect the capacity of the no-load transformer |
kVA |
one thousand two hundred and fifty |
|||||||
|
nine |
Rated short-circuit breaking current (current limiting fuse) |
kV |
thirty-one point five | ||||||
|
ten |
Rated transfer current |
A |
one thousand and six hundred | ||||||
|
eleven |
mechanical life |
time |
two thousand |
two thousand | |||||
|
serial number |
Name |
unit |
Parameters |
|
one |
Fracture distance |
mm
|
≥212 |
|
two |
Interphase center distance |
one hundred and seventy | |
|
three |
Just open and close speed |
m/s |
>5 |
|
four |
Positive pressure of the spring between the main contact blade and the contact |
N |
230±23 |
|
five |
Closing operation torque |
N.M |
80-100 |
|
six |
Three phase closing at different stages |
mm |
≤3 |
|
seven |
Three phase disconnection at different stages |
≤3 | |
|
eight |
The inherent opening time of the separation release device |
ms |
40~65 |
|
nine |
main circuit resistance |
μΩ |
≤100 |
|
Transformer capacity (KVA) |
one hundred |
one hundred and twenty-five |
one hundred and sixty |
two hundred |
two hundred and fifty |
300/
thirty-one point five |
four hundred |
five hundred |
six hundred and thirty |
750/
eight hundred |
one thousand |
one thousand two hundred and fifty |
|
Rated current of fuse (A) |
sixteen |
sixteen |
sixteen |
twenty |
twenty-five |
thirty-one point five |
forty |
fifty |
sixty-three |
eighty |
eighty
one hundred |
one hundred
one hundred and twenty-five |
NAL12 series technical assembly drawing