The FZN16A-12 series indoor AC high-voltage load switch fuse combination device meets the international and national standards of GB3804-90 "3-63kV AC voltage load switch" and IEC420 "AC high-voltage load switch fuse combination device" in terms of performance.
The FZN16A-12 series indoor high-voltage vacuum load switch is suitable for use in 6-10kV three-phase AC 50Hz power grids as a means of breaking load currents and closing short-circuit currents; Especially suitable for places that require oil-free, non maintenance, and frequent operation.
This product has an independent isolation fracture surface; The manual operation force is small, and it can be equipped with two types of vacuum arc extinguishing chambers: ceramic tube or glass tube. It is an ideal product for oil-free high-voltage switches and equipment upgrades.


Technical parameters of FZN16A-12 series vacuum load switch load switch:
| serial number |
Name |
Unit |
Parameters |
| one |
rated voltage |
kV |
twelve |
| two |
rated current |
A |
six hundred and thirty |
| three |
Rated Active load breaking current |
A |
six hundred and thirty |
| four |
Rated closed-loop breaking current |
A |
six hundred and thirty |
| five |
5% rated active load breaking current |
A |
thirty-one point five |
| six |
Rated cable charging breaking current |
A |
ten |
| seven |
Breaking current of rated no-load transformer |
A |
1250KVA transformer air cut current |
| eight |
1-minute power frequency withstand voltage (effective value) To the ground, alternating |
kV |
42/48 |
| nine |
Full wave lightning impulse withstand voltage (peak value) To the ground, alternating |
kV |
75/85 |
| ten |
Rated peak withstand current |
kA |
fifty |
| eleven |
Rated short-time withstand current |
kA/S |
20/3 |
| twelve |
Rated short-circuit closing current |
kA |
fifty |
| thirteen |
Rated current breaking times |
time |
ten thousand |
| fourteen |
mechanical life |
time |
ten thousand |
| fifteen |
Allowable cumulative thickness of contact wear |
mm |
three |
| sixteen |
Interphase center distance |
mm |
two hundred and ten |
| seventeen |
Manual operation for distance |
N.M |
<100 |
| eighteen |
Dimensions: Width X Height X Depth |
mm |
700×800×300 |
Technical parameters for assembly and adjustment of vacuum arc extinguishing chamber of FZN16A-12 series vacuum load switch:
| serial number |
Name |
Unit |
Parameters |
| one |
contact gap |
mm |
8+1 |
| two |
Contact itinerary |
mm |
3+1 |
| three |
Average closing speed |
m/s |
0.6±0.2 |
| four |
Average opening speed |
m/s |
1±0.2 |
| five |
Non synchronous opening and closing of three-phase contacts |
ms |
≤2 |
| six |
Contact closing bounce time |
ms |
≤2 |
| seven |
Distance between charged bodies and relative ground |
mm |
≥125 |
| eight |
Main circuit resistance between upper and lower brackets |
μ Ω |
≤60 |