| Product name: | ZFN16-12 series indoor AC high-voltage vacuum load switch | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor high-voltage load switch | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
serial number |
name |
unit |
parameter |
| one |
rated voltage |
KV | twelve |
| two |
Maximum operating voltage |
KV | twelve |
| three |
rated frequency |
Hz | fifty |
| four |
rated current |
A | six hundred and thirty |
| five |
Rated Active load breaking current |
A | six hundred and thirty |
| six |
Rated closed-loop breaking current |
A | six hundred and thirty |
| seven |
5% rated active load breaking current |
A | thirty-one point five |
| eight |
Rated number of cable charging disconnections |
A | ten |
| nine |
Rated capacitor breaking current |
A | four hundred |
| ten |
Rated no-load transformer breaking current |
A | 6000KVA transformer no-load current |
| eleven |
1-minute power frequency withstand voltage (effective value) to ground, phase to phase, vacuum break/isolation break |
KV | 42/48 |
| twelve |
Full wave lightning impulse withstand voltage (peak) to ground, phase to phase, vacuum break/isolation break |
KV | 75/85 |
| thirteen |
Rated short-time withstand current (thermal stability) |
KV/S | 20/3 |
| fourteen |
Rated peak withstand current (dynamic stability) |
KA | fifty |
| fifteen |
Rated short-circuit closing current |
KA | fifty |
| sixteen |
Rated current breaking times |
time |
ten thousand |
| seventeen |
mechanical life |
time |
ten thousand |
| eighteen |
Allowable cumulative thickness of contact wear |
mm | three |
| nineteen |
Opening and closing operation torque (force) |
Nm/(N) | 175(350) |
|
serial number |
name |
unit |
parameter | |
| one |
rated voltage |
KV | twelve | |
| two |
Maximum operating voltage |
KV | twelve | |
| three |
rated frequency |
Hz | fifty | |
| four |
Maximum rated current of fuse |
A | one hundred and twenty-five | two hundred |
| five |
Rated transfer current |
A | two thousand | three thousand one hundred and fifty |
| six |
The opening time of the fuse triggered switch |
ms | 35±5 | |
| seven |
Rated short-circuit breaking current (expected effective value) |
KA | thirty-one point five | |
| eight |
Rated short-circuit closing current (expected peak) |
KA | eighty | |
| nine |
1-minute power frequency withstand voltage (effective value) to ground, phase to phase, vacuum break/isolation break |
KV | 42/48 | |
| ten |
Full wave lightning impulse withstand voltage (peak) to ground, phase to phase, vacuum break/isolation break |
KA | 75/85 | |
| eleven |
Fuse impactor output energy |
J | 2-5 | |
| model | rated voltage | Fuse rated current | Rated breaking current | Rated current of melt |
| SDLAJ | twelve | forty | fifty | 6.3,10,16,20,25,31.5,40 |
| SFLAJ | one hundred | 50,63,71,80,100 | ||
| SKLAJ | one hundred and twenty-five | one hundred and twenty-five |
| serial number | project | unit | parameter |
| one | contact gap | mm | 8+1 |
| two | Contact profile | mm | 3+1 |
| three | Average closing speed | m/s | 0.6±0.2 |
| four | Average opening speed | m/s | 1±0.2 |
| five | Non synchronous opening and closing of three-phase contacts | ms | ≤2 |
| six | Contact closing bounce time | ms | ≤2 |
| seven | Distance between charged bodies and relative ground | mm | ≥125 |
| eight | Main circuit resistance of upper and lower brackets | μΩ | ≤60 |
Outline drawing

1. Closing spring
2. Operating mechanism
3. Guiding sleeve
4. Adjust the screw sleeve
5. Opening buffer pad
6. Opening buffer spring
7. Bracket
9. Insulators
10 upper brackets
11. Vacuum arc extinguishing chamber
12. Insulation holder
13. Lower bracket
14 Insulated push-pull rod

1. Closing spring
2. Operating mechanism
3. Guiding sleeve
4. Adjust the bolt
5. Opening buffer pad
6. Opening spring
7. Bracket
8. Insulators
9. Isolation knife
10. Upper bracket
11. Vacuum arc extinguishing chamber
12. Insulation holder
13. Lower bracket
14. Insulated push-pull rod
15. Melting tube
16. Screw
17. Nut
18. Grounding knife
1. Combination appliance
2. Φ 20 steel pipe (to be provided by the user)
3. Bend connection
4. Operating mechanism
5. Operating handle
6. Connect