GV4043 series switch type electric valve
Material Description
Valve body material: forged brass
Valve stem material: brass
Sealing material: Nitrile rubber (NBR)
Drive chassis: stainless steel
Drive cover: aluminum alloy
Product Overview
The Gv4303 series electric valve is used to control the opening or closing of pipelines in central air conditioning and heating systems, achieving the purpose of controlling room temperature. The control valve is driven by a unidirectional hysteresis synchronous motor with a spring reset. When the valve is not working, it is in a normally closed state. When it needs to work, the temperature controller provides a valve opening signal to connect the electric valve to the AC power supply and activate it. When the valve is opened, chilled water or hot water enters the fan coil unit to provide air conditioning or heating for the room; When the room temperature reaches the set value of the thermostat, the thermostat cuts off the power to the electric valve, and the reset spring closes the valve, thereby cutting off the water flow into the fan coil. By closing and opening the valve, the room temperature is always maintained within the temperature range set by the thermostat.
The GV4303 series electric valve can be optionally equipped with an auxiliary switch for controlling other equipment; And different connection forms and applicable voltages can be selected to meet different needs.
The GV4303 series electric valve is flexible in operation, reliable and durable, with low working noise, and can withstand high temperature and high humidity environments commonly found in concealed fan coil units.
GV4043 series switch type electric valve specifications and main data
| Product Model |
Name |
Kv value |
Configuration |
Configuration |
| V4043A1671B |
Fan coil valve/two-way |
six point eight |
3/4"BSPT/220V/50Hz |
54KPa |
| V4043C1222B |
Fan coil valve/two-way/cable |
three |
1/2 "horn tube/220V/50HZ |
136KPa |
| V4043C1347B |
Fan disc valve/two-way |
three |
1/2"BSPT/220V/50Hz |
136KPa |
| V40431354B |
Fan disc valve/two-way |
three |
1/2"BSPT/220V/50Hz |
136KPa |
| V4043C1362B |
Fan disc valve/two-way |
six point eight |
3/4"BSPT/220V/50Hz |
54KPa |
| V4043C1370B |
Fan disc valve/two-way |
six |
1/2"BSPT/220V/50Hz |
136KPa |
| V4043A1704B |
Fan disc valve/three-way valve |
six |
3/4"BSPT/220V/50Hz |
68KPa |
| V40431668B |
Fan disc valve/three-way valve |
six |
1/2"BSPT/220V/50Hz |
68KPa |
| V4043C1742B |
Fan disc valve/three-way valve |
six |
1/2"BSPT/220V/50Hz |
136KPa |
Installation instructions
1. The installation of normally closed two-way valves and diversion three-way valves is shown in Figure 1, Figure 2, and Figure 3.
For high-rise buildings, pressure reducing valves should be installed on the bottom branch pipes.
2. The motor casing should prevent water from seeping in. When the valve is installed in a horizontal pipeline, the angle between the installation position and the vertical plane should not exceed 85 ℃ (see Figure 4).
3. When the valve is installed on a vertical pipeline, the motor casing must prevent dripping water from seeping in.
4. Manual operating lever: When the manual lever is slowly moved in the direction of the arrow and pressed into the notch, the valve is in a normally open state. Whenever the current first passes through the electric valve, the manual lever will be reset to the automatic position.